E12
Mysa External Floor Sensor Short Circuit

Thermostat shows E12 and reports a floor sensor short or extremely high temperature reading.

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Floor sensor cable shorted together, Moisture ingress into sensor junction box, Crushed sensor cable under flooring

How to Fix / Troubleshooting

Safety first: Turn OFF power at the breaker before working on sensor wiring.

Steps to diagnose:

  • Disconnect sensor at thermostat: Remove the two floor sensor wires from the thermostat terminals.
  • Measure resistance: Use a multimeter across the sensor leads. A reading near 0 ohms indicates a shorted cable or sensor.
  • Inspect accessible cable runs: Check any exposed sections of the sensor cable for damage, staples, or pinching.
  • Dry out junction boxes: If the sensor passes through a junction box, open it and check for moisture. Dry thoroughly and re-test.

If the sensor remains shorted, replace the floor sensor probe. If a new sensor still results in E12, the thermostat’s sensor input circuit may be damaged and the thermostat should be replaced.