Controller displays E19, generator shuts down with high exhaust temperature warning
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Possible Causes
How to Fix / Troubleshooting
Safety first: Turn controller to OFF, open the generator AC breaker, and allow the exhaust system to cool completely before touching it.
- Inspect exhaust outlet: Ensure the exhaust termination is not blocked by snow, ice, vegetation, or animal nests. Clear any obstructions.
- Check muffler and piping: Look for crushed sections of exhaust pipe, severe rust, or signs of internal collapse in the muffler.
- Verify clearances: Confirm that the generator is installed with proper clearance from walls and structures so exhaust can dissipate.
- Inspect exhaust temperature sensor: Locate the sensor on or near the exhaust manifold. Check wiring and connector for heat damage or disconnection.
- Replace sensor if faulty: If wiring is intact but E19 recurs with normal exhaust flow, replace the exhaust temperature sensor.
Do not operate the generator with a restricted exhaust; this can cause carbon monoxide buildup and engine damage.