E16
JCB Phase Rotation / Phase Sequence Fault

E16 displayed; controller indicates phase sequence or phase rotation error and refuses to close to load.

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Incorrect phase wiring at generator terminals, Mis‑phased connection to ATS, Internal alternator reconnection error after service

How to Fix / Troubleshooting

Safety: Work on three‑phase connections only when fully isolated from mains and generator. Incorrect phase rotation can damage motors.

  • Verify phase sequence: Use a phase rotation meter at the generator output and at the ATS/load side to confirm correct rotation (e.g., L1‑L2‑L3).
  • Inspect terminal connections: In the JCB alternator terminal box, confirm that phases are connected to the correct labeled terminals and match the wiring diagram.
  • Check ATS wiring: Ensure the automatic transfer switch input from the generator is wired in the same phase order as the mains supply.
  • Correct wiring: If rotation is reversed, swap any two phases at the generator output or ATS input (not both) to restore correct sequence.
  • Reset alarm: Clear E16 and perform a test transfer under supervision.