E15
Kubota Controller Communication Bus Failure

Generator controller shows E15 and logs 'CAN Communication Error' or 'Controller Communication Fault'.

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Damaged CAN bus wiring, Loose controller connectors, Faulty expansion module, Electrical noise or grounding issues

How to Fix / Troubleshooting

Safety first: Turn OFF the generator and disconnect battery power before unplugging or plugging any control modules.

  • Inspect CAN wiring: Locate the twisted pair CAN bus wires between the Kubota main controller and any remote modules. Check for cuts, abrasions, or crushed sections.
  • Check terminations: Ensure that the CAN bus has proper termination resistors at each end as specified by Kubota. Missing or extra terminators can cause communication errors.
  • Secure connectors: Reseat all multi-pin connectors on the controller and modules. Look for bent pins or corrosion and clean as needed.
  • Grounding: Verify that the controller ground and chassis ground connections are tight and free of paint or rust. Poor grounding can introduce noise on the communication bus.
  • Module isolation: If multiple modules are on the bus, disconnect them one at a time to identify a faulty device that causes E15 when connected.
Advertisements

Repair Difficulty

Hard 4/5

Required Part

Generator Control Module
Check Price on Amazon

We may earn a commission from links on this page.

Advertisements