E15
Lifan Phase Sequence / Frequency Error

Lifan controller shows E15 and the generator will not transfer load.

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Incorrect wiring of phases at alternator or transfer switch, Engine speed out of tolerance, Faulty frequency sensing circuit in controller

How to Fix / Troubleshooting

Safety first: Open the transfer switch and lock it out. Turn OFF the generator and disconnect battery negative. Only qualified persons should work on live power systems.

  • Verify phase rotation: For three-phase Lifan units, use a phase rotation meter at the generator output lugs. Ensure the rotation matches the transfer switch and building system. If reversed, swap any two phase conductors at the generator terminals.
  • Check frequency: Start the generator in MANUAL with no load and measure frequency with a meter. Adjust the governor (per Lifan procedure) to bring frequency within 59–61 Hz for 60 Hz systems.
  • Inspect controller sensing wires: Ensure the voltage/frequency sensing leads from the alternator to the Lifan controller are correctly landed and not loose or damaged.
  • Controller fault: If wiring and frequency are correct but E15 persists, the controller’s sensing circuit may be defective. Replace the Lifan digital controller after confirming with factory diagnostics.