F25
Siemens Controller Communication Bus Fault

Controller displays F25 CAN Bus Communication Error; some functions may be disabled.

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Loose CAN bus connectors, Damaged communication cable, Incorrect termination resistors, Failed expansion module on CAN network

How to Fix / Troubleshooting

Safety first: Turn the controller to OFF and disconnect battery power before unplugging or plugging communication cables.

  • Inspect CAN wiring: Locate the CAN bus cable (often twisted pair) linking the Siemens controller to expansion modules (e.g., remote display, ATS interface). Check for cuts, abrasions, or crushed sections.
  • Reseat connectors: Unplug and firmly reconnect each CAN connector, ensuring locking tabs engage.
  • Check termination: Verify that termination resistors are installed only at the ends of the CAN bus, as specified by Siemens. Incorrect termination can cause F25.
  • Isolate faulty module: Disconnect modules one at a time from the CAN bus and power up the system. If F25 clears when a specific module is removed, that module may be defective and should be replaced.
  • Retest: After repairs, restore normal wiring and confirm that communication is stable and F25 does not reappear.
Advertisements

Repair Difficulty

Medium 3/5

Required Part

CAN Bus Communication Harness
Check Price on Amazon

We may earn a commission from links on this page.

Advertisements