Possible Causes

Incorrect wiring of centralized controller bus, Short or open circuit on central control line, Duplicate central address settings, Faulty central controller PCB

How to Fix / Troubleshooting

Safety first: Isolate power to all units and controllers before working on control wiring.

Steps:

  • Identify the central controller (e.g., Daikin intelligent touch controller or centralized wired remote) and its communication bus.
  • Check that the bus wiring polarity and terminal assignments match Daikin's diagram.
  • Inspect for any parallel connections or T-joints that are not allowed by the installation manual.

Technician tasks:

  • Measure bus resistance and continuity; locate and repair shorts or opens.
  • Check address settings on each indoor unit and the central controller to avoid duplication.
  • Temporarily disconnect the central controller; if the system runs normally, the controller or its wiring is suspect and may need replacement.