E9
Klimaire
Water Overflow / Drain Pan Full Protection (for models with float switch)
Indoor unit shows E9 and may stop operating; sometimes associated with condensate issues.
Advertisements
Possible Causes
Clogged condensate drain line, Blocked drain pan outlet, Faulty float switch in indoor unit, Improper indoor unit leveling causing poor drainage
How to Fix / Troubleshooting
Safety first: Turn OFF power before working near water and electrical components.
- Step 1 – Check for water leakage: Inspect around the indoor unit for water dripping or stains. Remove the front cover to view the drain pan.
- Step 2 – Clear drain line: Locate the condensate drain line exiting the indoor unit. Use a wet/dry vacuum at the drain outlet outside to suck out clogs. Alternatively, blow low-pressure air from the indoor side.
- Step 3 – Clean drain pan: Carefully clean the drain pan of slime, algae, and debris. Ensure the drain outlet is fully open.
- Step 4 – Check unit level: Use a level to confirm the indoor unit is slightly pitched toward the drain side. Adjust mounting if necessary.
- Step 5 – Inspect float switch: If equipped, locate the float switch in the drain pan. Ensure it moves freely and is not stuck in the up position. Replace the float switch if defective.
- Step 6 – Reset: After clearing the drain and ensuring the pan is dry, restore power and test. E9 should clear if the overflow condition is resolved.
Advertisements
Repair Difficulty
Easy
2/5
Required Part
Condensate Drain Line or Float Switch Assembly