E06
Toshiba
Outdoor Coil (Condenser) Temperature Sensor Fault
Outdoor unit stops; E06 displayed; may be associated with compressor not running.
Advertisements
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Advertisements
Possible Causes
Failed outdoor coil thermistor, Corroded thermistor connector, Damaged sensor harness, Faulty outdoor PCB sensor circuit
How to Fix / Troubleshooting
Safety first: Shut off power at the outdoor disconnect and verify with a meter before touching any wiring.
- Step 1 – Access outdoor coil sensor: Remove the outdoor unit top or side panel to expose the condenser coil. Locate the thermistor clipped to the coil tubing.
- Step 2 – Inspect sensor and harness: Check that the sensor is firmly attached to the coil and the wires are intact. Look for UV damage or rodent bites.
- Step 3 – Check connector: Trace the harness to the outdoor PCB and ensure the plug is fully seated and free of corrosion.
- Step 4 – Measure resistance: Disconnect the thermistor and measure resistance. Compare to Toshiba’s temperature–resistance chart. Replace if open, shorted, or significantly off-spec.
- Step 5 – Replace sensor: Install a new Toshiba-compatible outdoor coil sensor, clip it securely to the coil, and route the cable away from fan blades.
- Step 6 – Test operation: Reassemble, restore power, and run the unit in cooling and heating (if heat pump) to confirm the error does not return.