09
Biasi
Low Water Pressure / Water Pressure Switch Fault
Boiler shows error 09, will not fire, may indicate low system pressure or water shortage.
Advertisements
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Advertisements
Possible Causes
System pressure below minimum, Faulty water pressure switch or sensor, Leak in heating circuit, Blocked expansion vessel connection
How to Fix / Troubleshooting
Safety: Allow the boiler to cool before topping up. Do not exceed the pressure recommended in the Biasi manual (typically around 1.5 bar cold).
- Check pressure gauge: Look at the boiler's pressure gauge. If below 0.8–1.0 bar, the boiler may lock out.
- Top up via filling loop: Open the filling loop valves slowly and watch the gauge rise to about 1.2–1.5 bar, then close both valves firmly.
- Bleed radiators: After topping up, bleed radiators and recheck pressure, topping up again if necessary.
- Inspect for leaks: Look for visible water around radiators, valves, and under the boiler. Persistent pressure loss indicates a leak that must be repaired.
- Engineer checks: If pressure is correct but error 09 remains, a technician should test the water pressure switch or sensor and check the expansion vessel charge and connection.
Advertisements
Repair Difficulty
Medium
3/5
Required Part
Water Pressure Switch