Bradford White Micro-Zoning / Low Load Short Cycling

Boiler cycles on and off rapidly when only one small zone calls for heat.

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Zone too small for boiler minimum output, No buffer tank, Incorrect control strategy, Oversized boiler

How to Fix / Troubleshooting

Safety first: Turn off power before modifying control wiring or settings.

  • Step 1 – Confirm zone size: Identify which zone is calling when rapid cycling occurs (e.g., small bathroom loop, towel warmer).
  • Step 2 – Adjust boiler settings: If the control allows, lower the boiler’s minimum firing rate or adjust outdoor reset to reduce water temperature during mild weather.
  • Step 3 – Combine small zones (pro): A heating contractor may be able to pipe or control small zones so they operate together, increasing load.
  • Step 4 – Add buffer tank (pro): Installing a small buffer tank can increase system water volume and reduce cycling.
  • Step 5 – Review thermostat cycles per hour: Set thermostats to a lower cycles-per-hour setting if adjustable.

Note: This is a design issue more than a fault; solutions often involve system modifications.