E15
Bradford White External Module Communication Fault

Boiler shows E15 and may continue to run at reduced output; indicates communication error with optional modules (e.g., cascade or remote control).

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Loose communication cable, Incorrect wiring polarity on bus, Faulty remote or cascade module, Electrical noise on communication line

How to Fix / Troubleshooting

Safety first: Turn off power before working on low-voltage communication wiring.

  • Step 1 – Identify communication bus: Locate the terminals or connectors used for remote control, cascade, or BMS communication on the boiler control.
  • Step 2 – Check cable connections: Ensure all communication cables are firmly connected at both ends. Look for broken conductors or crushed cable jackets.
  • Step 3 – Verify polarity and addressing: Many communication buses require correct polarity (e.g., A/B, +/–) and unique addresses. Compare wiring and dip switch settings to the installation manual.
  • Step 4 – Isolate modules: Disconnect external modules one at a time to see if E15 clears. A single faulty module can bring down the bus.
  • Step 5 – Replace faulty module or cable: If a specific device or cable segment is identified as the cause, replace it with Bradford White-approved components.

Note: If the boiler operates normally otherwise, E15 may only affect remote monitoring or cascade functions.

Advertisements

Repair Difficulty

Medium 3/5

Required Part

Remote Interface / Cascade Module