Err 10
Burnham
Thermostat or Demand Signal Fault
Boiler shows “Err 10” and will not fire, often after thermostat or wiring changes
Advertisements
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Advertisements
Possible Causes
Open thermostat circuit, Incorrect wiring to TT or demand terminals, Faulty zone control relay, Internal control board failure
How to Fix / Troubleshooting
Safety first: Turn off power before opening the control compartment.
- Check thermostat: Ensure the thermostat is set to HEAT and the setpoint is above room temperature. Replace batteries if applicable.
- Inspect TT wiring: At the boiler, locate the thermostat (TT) or demand terminals on the Burnham control. Verify the low-voltage wires are firmly attached and not broken.
- Bypass test (for hydronic pros/competent DIYers): With power off, temporarily connect a jumper wire across the TT terminals. Restore power. If the boiler now fires without Err 10, the issue is in the thermostat or external controls.
- Check zone controls: If you have a Taco, Honeywell, or other zone control panel, verify its power and indicator lights. A failed relay may not be sending a call for heat to the boiler.
- Restore proper wiring: Remove the jumper and reconnect the thermostat or zone panel correctly. If Err 10 persists even with a direct jumper, the boiler control board may be defective and require replacement.