E15
Danstoker
Controller Communication Failure
Boiler controller indicates E15; communication error between Danstoker main controller and burner management system.
Advertisements
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Advertisements
Possible Causes
Loose communication cable (e.g., Modbus/Canbus) between panels, Faulty interface module, Incorrect address or protocol settings, Electrical interference or grounding issues
How to Fix / Troubleshooting
Safety: Isolate power before opening control panels.
- Inspect communication wiring: Check the data cable between the Danstoker boiler controller and the burner control or remote I/O. Tighten terminals and ensure shielded cable is correctly grounded at one end only.
- Verify settings: On both devices, confirm that communication parameters (baud rate, parity, address) match the Danstoker documentation.
- Check power to modules: Ensure any communication interface modules are powered and status LEDs indicate normal operation.
- Test with short cable: If possible, temporarily connect with a short known-good cable to rule out cable damage.
If E15 persists, the interface or controller PCB may need replacement by a qualified technician.
Advertisements
Repair Difficulty
Hard
4/5
Required Part
Communication Interface Module