E19
Danstoker Safety Interlock Open Circuit

Boiler display shows E19; safety chain open / general safety interlock fault.

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Tripped safety thermostat, Open door interlock switch on Danstoker boiler, Faulty emergency stop button, Broken wire in safety loop

How to Fix / Troubleshooting

Safety: Do not bypass safety devices. Isolate power before opening panels.

  • Check emergency stop: Ensure any emergency stop buttons near the Danstoker boiler are released. Reset if tripped.
  • Inspect safety thermostats: Locate manual reset safety thermostats on the boiler shell or flue. Once cooled, press reset buttons.
  • Door interlocks: Confirm that boiler access doors are fully closed and that any door switches are engaged.
  • Trace safety loop: Using the wiring diagram, check continuity through the safety chain from the controller. Repair any broken wires or replace faulty switches.

After restoring the safety loop, reset the controller. If E19 persists, the controller input may be defective.

Advertisements

Repair Difficulty

Medium 3/5

Required Part

Safety Thermostat
Check Price on Amazon

We may earn a commission from links on this page.

Advertisements