E17
Defro Room Thermostat / Control Signal Fault

Boiler shows E17, no response to room thermostat or OpenTherm controller, heating does not start.

Advertisements

Possible Causes

Open circuit in room thermostat wiring to Defro boiler, Incorrect control mode configuration in Defro PCB, Faulty room thermostat or OpenTherm controller, Loose low-voltage terminal connections

How to Fix / Troubleshooting

Safety: Isolate power before accessing the control terminals.

  • Check control settings: On the Defro control panel, verify that the correct control type (on/off thermostat, OpenTherm, or internal control) is selected according to the installation manual.
  • Inspect wiring: Open the terminal cover and check that the thermostat or controller wires are firmly connected to the correct low-voltage terminals.
  • Bridge test (on/off thermostats only): With power off, temporarily bridge the thermostat terminals at the boiler using a short wire. Restore power; if the boiler now responds and heats, the external thermostat or its wiring is faulty.
  • Controller check: If using a Defro modulating controller, try resetting it or testing with a known-good controller.
Advertisements

Repair Difficulty

Easy 2/5

Required Part

Defro room thermostat (compatible model)