A03
Hoval Flame Loss During Operation

Boiler locks out with A03, burner shuts down shortly after ignition or during operation

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Unstable gas supply pressure, Blocked or partially blocked burner, Faulty flame sensor (ionisation electrode), Combustion air supply or flue gas recirculation issue

How to Fix / Troubleshooting

Safety: Switch off power and close gas supply before opening the combustion chamber. Only trained personnel should work on combustion components.

  • Check flue and air intake: Ensure the concentric flue terminal is not blocked by leaves, snow, or debris. Verify that the air intake is clear and that flue joints are secure.
  • Inspect burner surface: Remove the burner assembly as per Hoval service instructions. Check for soot, corrosion, or debris on the premix burner surface. Clean gently with a soft brush; do not damage the mesh.
  • Clean ionisation electrode: Remove and clean the electrode tip. Check cable integrity and correct positioning in the flame.
  • Gas supply stability: If other gas appliances show issues or if the boiler frequently loses flame at high demand, have a technician measure dynamic gas pressure and adjust or report to the gas supplier.
  • If flame loss continues, a Hoval technician should perform a combustion analysis and check burner and gas valve settings.