E13
Keston Gas Valve Control Fault

Boiler shows E13, fan runs but ignition sequence does not start

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Gas valve coil failure, Loose gas valve connector, PCB output fault, Incorrect gas valve setting

How to Fix / Troubleshooting

Safety: All gas valve work must be carried out by a Gas Safe registered engineer. Isolate gas and power before starting.

User checks:

  • Confirm gas supply to the property is available and other gas appliances operate normally.
  • Do not attempt to adjust or tap the gas valve.

Engineer checks:

  • Check the electrical connector on the Keston gas valve for secure fit and no signs of overheating.
  • Measure resistance of the gas valve coil(s) and compare with manufacturer specifications; replace the valve if open or shorted.
  • During ignition attempt, measure control voltage at the gas valve terminals; if absent, suspect PCB fault.
  • After replacement, commission the boiler with a flue gas analyser and adjust gas valve settings as per Keston combustion instructions.
Advertisements

Repair Difficulty

Professional Required 5/5

Required Part

Gas Valve Assembly
Check Price on Amazon