E09
Klimosz High System Pressure / Expansion Fault

Boiler displays E09, pressure reading is very high or fluctuates rapidly.

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Failed expansion vessel on Klimosz boiler, Overfilled system, Faulty pressure relief valve, Blocked expansion vessel connection

How to Fix / Troubleshooting

Safety: High pressure can cause hot water discharge. Allow the system to cool before working on it.

  • Check pressure cold vs hot: Note the pressure when the system is cold and again when hot. If it rises above 2.5–3.0 bar when hot, the expansion vessel may be faulty.
  • Reduce pressure: Bleed water from a radiator or use the drain valve to bring pressure back to about 1.2 bar when cold.
  • Check expansion vessel charge: Isolate the boiler from the system and drain pressure to 0 bar. Measure the air charge at the expansion vessel Schrader valve (usually 0.8–1.0 bar). Re-pressurize with a pump if low, or replace the vessel if water comes out of the valve.
  • Inspect PRV outlet: Check if the pressure relief valve discharge pipe is dripping. If it leaks continuously, the PRV may be damaged and should be replaced.
  • Restart and monitor: Refill the system to correct pressure and observe operation. If E09 recurs, have a technician evaluate the expansion system.
Advertisements

Repair Difficulty

Medium 3/5

Required Part

Expansion Vessel
Check Price on Amazon