A22
Raypak
Inlet Water Temperature Sensor Fault
Boiler shows A22; unit may not modulate correctly or may shut down on temperature error.
Advertisements
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Advertisements
Possible Causes
Failed inlet temperature sensor, Loose sensor harness, Sensor out of position in well, Control board sensor circuit failure
How to Fix / Troubleshooting
Safety: Turn OFF power and allow the boiler to cool.
Steps:
- 1. Locate inlet sensor: Identify the sensor on the return/inlet header or sensor well labeled inlet or return.
- 2. Inspect and reseat wiring: Check for secure connections and no visible damage. Reseat the connector.
- 3. Verify sensor insertion: Confirm the sensor is fully seated in the well and clamped if required.
- 4. Compare temperatures: Use the control display to read inlet temperature and compare to a pipe surface thermometer. A large mismatch indicates a faulty sensor.
Replace the inlet temperature sensor if faulty. If A22 persists with a new sensor, the control board should be tested by a Raypak-qualified technician.