Boiler display shows A71; unit may lock out on safety chain fault.
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Possible Causes
How to Fix / Troubleshooting
Safety: A safety device has opened for a reason. Do not bypass safety switches for operation.
Steps:
- 1. Identify safety devices: Locate the high limit, rollout switch, flue spill switch, and any other safeties wired in series to the control.
- 2. Check manual reset devices: Some rollout or high limit switches have a small reset button. After the boiler has cooled, press each reset button once. If a device immediately trips again, shut the boiler down and investigate the cause (blocked flue, flame rollout, overheating).
- 3. Inspect wiring: Follow the safety circuit wiring. Look for loose spade connectors, broken wires, or corrosion.
If A71 remains after verifying all safeties are reset and wiring is intact, a faulty safety switch or control board input may be present. Have a qualified technician test and replace components as needed.
Repair Difficulty
Required Part
We may earn a commission from links on this page.