25
Rinnai
Condensate Drain Blockage
Boiler stops and shows error 25; condensate may be visible around the unit or in the base tray.
Advertisements
Possible Causes
Blocked condensate trap, Frozen condensate pipe, Sagging or improperly sloped condensate line, Debris or sludge in condensate hose
How to Fix / Troubleshooting
Safety first: Turn off power to the boiler. Condensate is mildly acidic; wear gloves and eye protection when handling.
- Inspect condensate trap: Locate the condensate trap at the base of the boiler. Place a container underneath, remove the trap, and empty it. Rinse thoroughly with clean water to remove sludge.
- Check condensate pipe routing: Ensure the pipe slopes continuously downward to the drain with no upward loops or sags that can hold water.
- Clear external termination: If the condensate discharges outside, check for ice, dirt, or blockages at the outlet. In freezing weather, thaw the pipe gently with warm (not boiling) water or a warm cloth.
- Reassemble and test: Refit the trap securely, restore power, and reset the boiler. Observe for leaks and confirm that condensate flows freely during operation.
- Persistent issues: If error 25 returns, have a technician inspect the condensate level sensor and internal drain passages.