E20
Sime
External Control / Room Thermostat Fault
Boiler displays E20, may indicate external control or thermostat fault
Advertisements
Possible Causes
Open-circuit room thermostat, Faulty external programmer, Broken low-voltage wiring, Incorrect wiring at control terminals
How to Fix / Troubleshooting
Safety first: Isolate power before working on control wiring.
- Check controls: Ensure the room thermostat and programmer are calling for heat (set to maximum temperature and constant on).
- Bypass test (engineer task): At the boiler's low-voltage control terminals, temporarily link the room stat contacts as per Sime instructions. If the boiler runs, the external control or wiring is faulty.
- Inspect wiring: Check for loose or damaged cables between the boiler and thermostat/programmer.
- Replace faulty control: Fit a compatible room thermostat or programmer if found defective.