E11
Weishaupt Return Temperature Sensor (NTC) Failure

Boiler indicates E11, return temperature sensor fault, boiler may cycle rapidly or shut down.

Advertisements

Possible Causes

Open or shorted return NTC, Loose sensor contact on return pipe, Damaged sensor cable, Fault on control board input

How to Fix / Troubleshooting

Safety first: Isolate power before accessing internal components.

  • Locate return sensor: The return NTC is usually clipped to the return pipe entering the boiler or inserted into a pocket.
  • Check mounting: Ensure the sensor is firmly attached and making good thermal contact with the pipe (use new thermal paste or clip if needed).
  • Inspect wiring: Follow the cable to the control board, checking for cuts or loose plugs. Reseat connectors.
  • Measure resistance: Compare the sensor resistance to the Weishaupt temperature/resistance chart. Replace if out of range.

When to call a professional: If the sensor is good but the fault remains, the control board may need professional diagnosis.

Advertisements

Repair Difficulty

Easy 2/5

Required Part

Return Temperature Sensor (NTC)
Check Price on Amazon