Worcester Bosch Blocked or Frozen Condensate Pipe

Boiler shows A1 and stops, often with gurgling noises, especially in cold weather.

Advertisements

Possible Causes

Frozen external condensate pipe, Blocked condensate trap, Sagging condensate pipe causing standing water, Incorrect condensate pipe fall

How to Fix / Troubleshooting

Safety first: Switch off the boiler at the control panel before working on the condensate pipe. Do not use naked flames or boiling water.

  • Locate the condensate pipe: This is usually a white or grey plastic pipe (21.5mm or 32mm) running from the boiler to a drain, often outside.
  • Check for freezing: In freezing weather, feel the external section. If it is very cold and the boiler shows A1, it may be frozen.
  • Thaw the pipe: Pour warm (not boiling) water along the length of the external pipe and trap area. You can also use a warm cloth wrapped around the pipe.
  • Reset the boiler: Once thawed, reset the boiler and check it runs normally.
  • Prevent recurrence: Insulate the external condensate pipe and, if possible, increase its diameter or reroute internally (by a professional) to reduce freezing risk.
Advertisements

Repair Difficulty

Easy 2/5

Required Part

Condensate Trap and Pipe
Check Price on Amazon