E11
Besenergy
Protective Earth (PE) Loss / Ground Continuity Fault
Display shows E11; charger will not start and may indicate a ground connection problem.
Advertisements
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Advertisements
Possible Causes
Open ground conductor in supply wiring, Loose ground lug inside charger, Corroded ground connection at service panel, Faulty ground detection circuit
How to Fix / Troubleshooting
Safety first: Do not use the charger until the ground fault is resolved. Turn OFF the breaker.
- 1. Visual inspection: With power OFF, remove the charger cover and verify that the green/yellow ground wire is securely attached to the ground terminal and metal chassis. Tighten if loose.
- 2. Check supply ground: Have a licensed electrician verify continuity of the ground conductor from the charger back to the main panel. Repair any breaks or loose terminations.
- 3. Inspect for corrosion: Look for rust or corrosion at the ground lug or bonding points. Clean and re-terminate as needed.
- 4. Test with meter (qualified): Measure resistance between the charger chassis and known good ground; it should be very low (near 0 ohms). High resistance indicates a poor ground connection.
- 5. Internal detection fault: If the ground is confirmed good but E11 persists, the ground detection circuit on the main control board may be faulty and require board replacement.
When to call a professional: Grounding issues must be corrected by a licensed electrician. Do not bypass or disable ground detection.