dF
Vissani Defrost Mode Indication (Normal Operation or Stuck Defrost)

Display shows dF or DEF; freezer may pause cooling briefly while code is shown.

Advertisements

Possible Causes

Normal automatic defrost cycle, Control board stuck in defrost, Defective defrost thermostat not resetting, Failed defrost timer logic on control board

How to Fix / Troubleshooting

Safety: No immediate hazard. Do not unplug during a normal defrost unless troubleshooting.

Steps:

  • Determine if normal: Many Vissani freezers briefly display dF during scheduled defrost. This should last 15–30 minutes and then return to normal display.
  • Monitor duration: If dF remains for more than 1 hour and the compressor does not restart, suspect a stuck defrost condition.
  • Power reset: Unplug the freezer for 5–10 minutes, then plug back in. If dF immediately returns and cooling does not resume, further diagnosis is needed.
  • Check defrost thermostat: Access the evaporator and test the defrost thermostat. If it remains closed when warm, it may be causing extended defrost.
  • Control board: If the thermostat is good, the main control board defrost logic may be faulty and require replacement.

Note: If temperatures remain safe and dF appears only occasionally, it is likely normal operation.