A06
Brötje
Fan / air pressure fault
Display shows A06, boiler does not start, fan symbol may flash
Advertisements
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Advertisements
Possible Causes
Defective flue fan, Blocked air intake or exhaust, Faulty air pressure switch, Damaged fan speed sensor or wiring
How to Fix / Troubleshooting
Safety: Isolate power before removing the combustion chamber cover. Do not operate the boiler with the cover removed.
- 1. Listen for fan operation: On a call for heat, the Brötje fan should start before ignition. If there is no sound, check the fan connector and supply voltage (qualified personnel only).
- 2. Inspect air intake and flue: Check the concentric flue for obstructions. Ensure the air intake is not blocked by insulation, dust, or insects.
- 3. Check air pressure switch and tubing: Locate the air pressure switch and silicone tubes connected to the fan or flue. Inspect for cracks, disconnections, or water in the tubes. Replace damaged tubes and ensure correct routing.
- 4. Test pressure switch: With a multimeter (technician), verify that the switch changes state when the fan runs. Replace the Brötje air pressure switch if it does not operate reliably.
- 5. Fan inspection: Remove the fan assembly and check for seized bearings, debris, or broken impeller blades. Replace the fan if noisy, seized, or not reaching speed.
Advertisements
Repair Difficulty
Hard
4/5