09
Immergas External Control / Thermostat Circuit Fault

Display shows 09, furnace does not respond to room thermostat or external controls

Advertisements

Possible Causes

Open or shorted room thermostat wiring, Incorrect thermostat connection, Faulty external control board or jumper missing

How to Fix / Troubleshooting

Safety: Isolate power before working on control wiring.

Steps:

  • 1. Check thermostat settings: Ensure the room thermostat or Immergas remote control is calling for heat and batteries (if any) are good.
  • 2. Inspect wiring: At the boiler terminal strip, verify that the thermostat wires are correctly connected to the designated terminals (e.g., TA, COM). Look for loose strands or shorts.
  • 3. Bypass test (technician or skilled DIY): With power off, temporarily fit a jumper wire across the room thermostat terminals. Restore power; if the boiler now responds, the thermostat or its wiring is faulty.
  • 4. External control modules: If using an Immergas proprietary controller (e.g., CARV2, Super CAR), check the bus connection and polarity. Replace the controller or cable if defective.
Advertisements

Repair Difficulty

Easy 2/5

Required Part

Room Thermostat or Remote Controller
Check Price on Amazon

We may earn a commission from links on this page.

Advertisements