Intergas Flow Temperature Sensor Overrange / Short Circuit

Code 6 displayed, boiler will not run, may be accompanied by very high temperature reading

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Shorted flow NTC sensor, NTC cable damaged and shorted to pipe, Faulty PCB input circuit, Sensor installed incorrectly

How to Fix / Troubleshooting

Safety first: Isolate power. Let the boiler cool before touching sensors or pipework.

Steps:

  • Inspect sensor and cable: Locate the flow NTC on the flow pipe. Check that the cable is not crushed under the casing or touching hot metal causing insulation damage.
  • Disconnect and test: With power off, disconnect the NTC from the PCB and measure its resistance. A very low resistance (near 0 Ω) indicates a shorted sensor.
  • Check PCB reading: If the sensor tests correctly but the boiler still shows an overrange fault, the PCB may be misreading the signal.

Remedy: Replace the flow NTC sensor if shorted. If replacing the sensor and cable does not resolve the issue, the Intergas main PCB will likely need replacement by a qualified technician.

Advertisements

Repair Difficulty

Medium 3/5

Required Part

Flow NTC sensor