Keeprite
Blower Stuck On
Indoor blower runs continuously even when thermostat is not calling for heat or fan.
Advertisements
Possible Causes
Fan set to ON at thermostat, Stuck blower relay on control board, Open limit switch, Miswired G terminal
How to Fix / Troubleshooting
Steps:
- Check thermostat fan setting: Ensure the fan is set to AUTO, not ON.
- Observe LED codes: If a limit fault code is present, the board may be running the blower for safety; troubleshoot the limit issue first.
- Test G circuit: Disconnect the G wire at the control board. If the blower stops, the thermostat or wiring is holding G energized.
- Check control board: If blower runs with G disconnected and no fault codes, the blower relay on the board may be stuck and the board will need replacement.
Always turn off power before disconnecting or reconnecting thermostat wires.