24
Tempstar
Open or Shorted Secondary (24V) Circuit
LED flashes code 24; thermostat calls are not recognized, furnace does not respond to heat demand.
Advertisements
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Advertisements
Possible Causes
Blown low-voltage fuse on Tempstar control board, Shorted thermostat cable, Miswired thermostat, Shorted humidifier or outdoor unit contactor coil on R-C circuit
How to Fix / Troubleshooting
Safety: Turn off power to the furnace before checking wiring or replacing fuses.
- Step 1 – Inspect 3–5A board fuse: Locate the automotive-style blade fuse on the Tempstar control board. If it is blown, replace it with the same amperage rating only.
- Step 2 – Isolate thermostat wiring: Disconnect all thermostat wires from the R, W, Y, G, and C terminals. Install a new fuse and restore power. If the fuse holds, the short is likely in the thermostat cable or connected accessories.
- Step 3 – Test thermostat cable: Reconnect wires one at a time (starting with R and W for heat) and observe if the fuse blows. If it blows when a specific wire is connected, inspect that cable run for staples, cuts, or pinches and repair or replace.
- Step 4 – Check external devices: If a humidifier, air cleaner, or outdoor unit is powered from R and C, disconnect those leads and test again. Replace any shorted coils or wiring.
- Step 5 – Verify thermostat wiring: Confirm the thermostat is wired according to the Tempstar wiring diagram and thermostat instructions. Correct any miswiring.
Advertisements
Repair Difficulty
Medium
3/5
Required Part
Tempstar Furnace Control Board Fuse
Check Price on Amazon
We may earn a commission from links on this page.
Advertisements