No Power to Furnace
Furnace will not start at all; no blower, no inducer, no LED lights on Tempstar control board.
Advertisements
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Advertisements
Possible Causes
Tripped furnace breaker, Off or faulty furnace service switch, Open blower door safety switch, Failed 120V to 24V Tempstar transformer
How to Fix / Troubleshooting
Safety: Use caution when working around 120V circuits. Turn off the breaker before removing covers.
- Step 1 – Check breaker and switch: Verify the furnace breaker in the electrical panel is ON. Locate the furnace service switch and ensure it is ON.
- Step 2 – Verify door switch: Remove and reinstall the blower door, ensuring it fully depresses the door safety switch. A misaligned door can cut power to the board.
- Step 3 – Test incoming power: With a multimeter and power ON, carefully measure voltage at the furnace line terminals (L1 and neutral). You should see ~120V. If not, there is an upstream electrical issue.
- Step 4 – Check transformer: With power off, inspect the Tempstar transformer for burns or loose wires. With power on, verify 120V on the primary and ~24V on the secondary. Replace the transformer if 24V is missing.
Advertisements
Repair Difficulty
Medium
3/5
Required Part
Tempstar Furnace Transformer