E08
Wolf
Pressure Switch Stuck Open
Furnace displays E08 and will not complete ignition; inducer may start and stop.
Advertisements
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Advertisements
Possible Causes
Blocked intake or exhaust vent, Failed pressure switch diaphragm, Loose or cracked pressure tubing, Condensate blockage in pressure switch port (on condensing Wolf models)
How to Fix / Troubleshooting
Safety: Turn off power and gas. Do not blow into pressure switch ports with your mouth; use dry air only.
- Vent inspection: Check both intake and exhaust terminations for obstructions such as ice, snow, or debris. Clear any blockage and ensure proper clearances per Wolf installation instructions.
- Pressure tubing: Remove the rubber tubing from the pressure switch and inducer housing. Inspect for water, cracks, or kinks. Replace if brittle or damaged. Use a small piece of wire or drill bit (by hand) to gently clear the port on the inducer housing if clogged.
- Condensate drains (if applicable): On condensing Wolf furnaces, ensure the condensate trap and drain lines are not blocked. A backed-up trap can affect pressure readings.
- Switch test: A technician can test the pressure switch with a manometer and continuity meter. If the switch does not close at the specified negative pressure, replace it with the correct Wolf pressure switch model.