E12
Wolf
Low-Voltage Power Fault (24V Transformer/Control Fuse)
Furnace shows E12 and will not start; 24V control power may be absent.
Advertisements
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Advertisements
Possible Causes
Blown low-voltage fuse on Wolf control board, Shorted thermostat wiring, Failed 24V transformer, Miswired accessory drawing excessive current
How to Fix / Troubleshooting
Safety: Turn off power before replacing fuses or working on wiring.
- Inspect fuse: Locate the low-voltage automotive-style fuse (typically 3–5A) on the Wolf control board. If blown, replace with the same type and rating only.
- Check for shorts: Before restoring power, inspect thermostat and accessory wiring (humidifier, air cleaner) for bare wires touching metal or each other. Repair any damaged sections.
- Transformer test: With power on and fuse intact, measure voltage at the transformer secondary (usually 24VAC). If no output, the Wolf 24V transformer is likely failed and must be replaced.
- Monitor fuse: If the new fuse blows again immediately, there is still a short in the low-voltage circuit that must be located and corrected before further operation.
Advertisements
Repair Difficulty
Medium
3/5
Required Part
Wolf 24V Transformer
Check Price on Amazon