E10
Pahlen External Control / Thermostat Input Fault

Heater displays E10 and will not fire; often associated with external control or thermostat issues.

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Open or shorted external thermostat connection, Incorrect wiring from pool automation to Pahlen heater, Misconfigured control mode on Pahlen controller, Faulty external temperature sensor (if used)

How to Fix / Troubleshooting

Safety first: Turn off power to the heater before adjusting wiring.

Step-by-step checks:

  • Verify control mode: On the Pahlen user interface, confirm whether the heater is set to internal thermostat mode or external control (e.g., pool automation). Set it according to your installation.
  • Inspect external control wiring: Open the control compartment and locate the low-voltage terminals for external thermostat/automation. Check that wires are firmly attached and not shorted together or to ground.
  • Bypass test (if allowed): If the heater is supposed to be controlled externally, temporarily disconnect the external wires and configure the heater to internal control. Set a temperature above current water temperature and see if the heater starts. If it does, the issue is with the external control system.
  • Check external sensor (if installed): If a Pahlen remote water sensor is used, test its resistance and compare to the temperature chart. Replace if out of range.

When to stop: If you are unsure about low-voltage wiring or automation integration, consult a pool professional or Pahlen service technician.