Gosund No Heat Call from Thermostat

Thermostat has power but will not turn on heating when room is below setpoint

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Loose or broken W (or W1) wire, Misconfigured system type (set to cool‑only), Failed heat relay on thermostat, Open safety limit or issue in furnace preventing heat

How to Fix / Troubleshooting

Warning: Turn off power to the furnace before handling wiring.

  • Step 1 – Verify settings:
    • Ensure the thermostat is set to Heat mode and the setpoint is above room temperature.
    • Check that system type is correctly set (conventional vs heat pump).
  • Step 2 – Inspect W wiring:
    • Confirm the W/W1 wire is securely connected at both thermostat and furnace board.
  • Step 3 – Test furnace response:
    • At the furnace board, jumper R to W; if the furnace starts heating, the issue is likely the thermostat or its wiring.
  • Step 4 – Measure W output:
    • With a heat call active, measure voltage between W and C at the thermostat; should be ~24VAC.
    • If no voltage, the thermostat’s heat relay is likely defective.
  • Step 5 – Replace thermostat if W output is bad:
    • Replace the thermostat if it cannot provide 24VAC on W with a heat call.