Lo
Heatit Measured Temperature Below Sensor Range

Display shows "Lo" instead of temperature and heating does not start

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Floor or room extremely cold (below sensor spec), Sensor cable routed outdoors or into unheated cavity, Wrong sensor type configured, Sensor partially open circuit

How to Fix / Troubleshooting

Safety first: Turn OFF power at the breaker before accessing wiring.

Steps to troubleshoot:

  • 1. Verify actual temperature:
    • Use an external thermometer to measure room or floor temperature.
    • If the environment is not extremely cold, the sensor reading is likely faulty.
  • 2. Check sensor configuration:
    • Ensure the correct sensor type (NTC value) is selected in the installer menu.
  • 3. Inspect sensor routing:
    • Confirm the sensor cable is routed only within the heated area and not into an unheated void or outside wall.
  • 4. Measure sensor resistance:
    • Disconnect the sensor and measure resistance; compare with the NTC curve.
    • If resistance is much higher than expected, replace the sensor.