E10
Schneider Electric
Equipment Communication Bus Failure
Thermostat shows E10 and indicates communication loss with HVAC equipment or zone controller.
Advertisements
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Advertisements
Possible Causes
Open or shorted RS‑485 / Modbus / proprietary bus wiring, Reversed polarity on A/B or +/− terminals, Incorrect baud rate or address configuration, Failed communication transceiver on thermostat PCB
How to Fix / Troubleshooting
Safety: De‑energize the control circuit before adjusting bus wiring.
Steps:
- Identify the communication bus terminals on the thermostat (e.g., A/B, +/−, D1/D2) and on the Schneider Electric controller or HVAC interface module.
- Verify that the wires are landed on the correct polarity terminals at both ends; reverse A/B or +/− if necessary according to the wiring diagram.
- Inspect the cable for damage, kinks, or shorts. Use twisted pair cable recommended by Schneider Electric for RS‑485/Modbus.
- Check that only the devices at the ends of the bus have termination resistors enabled, if required by the system design.
- Enter the thermostat configuration and confirm that the protocol (e.g., Modbus RTU), baud rate, parity, and device address match the controller settings.
- If all wiring and settings are correct and E10 persists, the communication transceiver chip on the thermostat or controller may be faulty; contact a professional to test and replace the affected device.