E01
Aksa Emergency Stop Active / External Shutdown

Generator will not start; controller shows E01 and immediately aborts cranking.

Advertisements

Possible Causes

Emergency stop button engaged, External shutdown circuit open, Faulty emergency stop switch, Wiring harness open between E‑stop and controller

How to Fix / Troubleshooting

Safety first: Ensure the generator is in OFF mode, battery negative is disconnected if you will touch wiring, and the unit cannot start automatically.

  • Check emergency stop button: Locate the red E‑STOP on the Aksa enclosure door or control panel. Turn or pull it to release. Reset the controller and attempt a start.
  • Inspect external shutdown loop: Many Aksa standby sets have a remote shutdown input (fire alarm, remote E‑stop). Verify any remote E‑stop stations are reset and that the wiring is intact.
  • Check controller inputs: On the Aksa controller I/O terminals, verify the emergency stop / remote stop input is closed using a multimeter. Repair any broken wires or loose terminal screws.
  • Test the E‑stop switch: With power isolated, disconnect the E‑stop switch leads and check continuity while pressing/releasing. Replace the switch if it does not change state reliably.
  • Clear code and retest: Reconnect wiring, reset the controller, and attempt a manual start. If E01 persists, the controller input may be faulty and professional service is recommended.