E07
Aksa
Engine Underspeed / Failure to Accelerate
Generator shuts down during cranking or shortly after start; controller shows E07 Underspeed / Failure to Reach Rated Speed.
Advertisements
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Advertisements
Possible Causes
Fuel restriction, Weak fuel actuator, Incorrect governor gain settings, Mechanical engine problem (low compression)
How to Fix / Troubleshooting
Safety first: Disable automatic start and avoid extended cranking to prevent starter damage.
- Check fuel filters: Replace clogged primary and secondary fuel filters on the Aksa engine. Prime the system thoroughly.
- Inspect fuel actuator linkage: Ensure the actuator lever moves smoothly from idle to full fuel. Remove any obstructions and check for loose linkages.
- Verify no heavy load is connected: Ensure the automatic transfer switch (ATS) is not forcing load during start. The generator should reach rated speed before taking load.
- Controller parameters: In the Aksa controller, verify rated speed and underspeed thresholds are correct. Only trained personnel should adjust governor PID settings.
- Engine health: If the engine runs but cannot reach speed even with clean fuel supply, internal engine issues may exist. Arrange for compression and injector testing by a technician.
Advertisements
Repair Difficulty
Hard
4/5
Required Part
Electronic Governor Actuator