E16
Aksa Low Fuel Level Protection

Generator shuts down; controller shows E16 Low Fuel Level Alarm / Shutdown.

Advertisements

Possible Causes

Fuel tank level below sensor threshold, Faulty fuel level sender, Wiring fault between sender and controller, Incorrect level calibration

How to Fix / Troubleshooting

Safety first: Turn off automatic start and keep ignition sources away from fuel.

  • Confirm actual fuel level: Use the mechanical gauge on the Aksa base tank or dip the tank (if safe and allowed). Refill if low.
  • Inspect fuel level sender: Locate the level sender on the tank top. Check for loose mounting screws and damaged float arm.
  • Check wiring: Follow the sender wires to the controller. Repair any cuts, abrasions, or loose terminals.
  • Calibrate level input: In the controller configuration, verify the sender type (resistive/4–20 mA) and calibration points. Adjust if necessary (qualified personnel only).
  • Replace sender if faulty: If resistance or current output does not change with fuel level, replace the sender with an Aksa‑compatible unit.
Advertisements

Repair Difficulty

Easy 2/5

Required Part

Fuel Level Sender
Check Price on Amazon

We may earn a commission from links on this page.