E18
Aksa
Earth Leakage / Ground Fault Protection
Generator shuts down; controller shows E18 Earth Fault / Ground Fault.
Advertisements
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Advertisements
Possible Causes
Insulation failure in cables, Moisture ingress in alternator, Incorrect neutral‑earth bonding, Faulty earth fault relay or CT
How to Fix / Troubleshooting
Safety first: De‑energize the generator and isolate from all loads. Ground faults can be dangerous.
- Visual inspection: Check generator output cables, junction boxes, and ATS for signs of moisture, burns, or damaged insulation.
- Insulation resistance test: Using a megohmmeter (qualified personnel only), test phase‑to‑earth and neutral‑to‑earth resistance. Identify and repair low‑resistance paths.
- Check alternator for moisture: Inspect the Aksa alternator for condensation or water ingress. Dry the unit thoroughly before re‑energizing.
- Verify earth fault CT and relay: Ensure the earth fault CT is correctly installed and wiring to the controller is intact. Replace a faulty relay or CT if readings are inconsistent.
- Re‑test: After repairs, clear the E18 alarm and run the generator under supervision while monitoring earth fault status.