E005
Atlas Copco Engine Underspeed / Underfrequency Trip

Controller displays E005 Underspeed and the generator trips off load

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Excessive load applied, Fuel supply restriction, Faulty speed governor or actuator, Incorrect speed sensor signal

How to Fix / Troubleshooting

Safety first: Ensure the generator is isolated from the load before testing. Avoid running the unit for long periods at low frequency as it can damage connected equipment.

  • Check load level: Review the automatic transfer switch (ATS) or load breakers. Confirm that the total kW and kVA do not exceed the Atlas Copco generator rating. Shed non‑essential loads and retest.
  • Inspect fuel supply: Verify the main fuel tank has adequate fuel. Check for closed isolation valves, kinked hoses, or clogged pre‑filter/water separator. Replace fuel filters if service is overdue.
  • Observe engine response: Start the generator in manual mode with no load. If it still runs below rated speed/frequency, suspect a governor or actuator issue.
  • Check speed sensor and wiring: As with overspeed faults, inspect the magnetic pickup and harness for damage or loose connections that could cause intermittent speed readings.
  • Controller calibration: Confirm the rated frequency (50/60 Hz) and speed parameters in the controller match the generator nameplate.

Persistent underspeed under normal load requires governor calibration or repair by an authorized technician.