E029
Atlas Copco Breaker / ATS Position Feedback Error

Controller shows E029 ATS Feedback Fault / Breaker Position Mismatch

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Faulty auxiliary contacts on breaker, Miswired ATS feedback signals, Stuck breaker mechanism, Controller logic misconfiguration

How to Fix / Troubleshooting

Safety first: Work on breakers and ATS only with all sources isolated and locked out. Mechanical interlocks must be respected.

  • Check actual positions: Verify physically whether the generator and mains breakers or ATS contactors are open or closed.
  • Inspect aux contacts: Locate the auxiliary contacts that report breaker status to the controller. Test continuity in open and closed positions and replace if faulty.
  • Verify wiring: Compare feedback wiring to the Atlas Copco schematic to ensure the correct signals are connected to the controller inputs.
  • Review controller logic: Confirm that the controller is programmed for the correct type of ATS/breaker scheme.

Correct feedback is essential for safe automatic operation; resolve E029 before returning to service.

Advertisements

Repair Difficulty

Hard 4/5

Required Part

Breaker Auxiliary Contact Block
Check Price on Amazon

We may earn a commission from links on this page.

Advertisements