EXER
Briggs & Stratton Failed Exercise Run

Controller displays EXER FAIL or EXERCISE FAILED after a scheduled exercise period.

Advertisements

Possible Causes

Battery too weak to crank during exercise, Fuel supply off at time of exercise, Prior latched fault preventing auto start, Controller exercise schedule misconfigured

How to Fix / Troubleshooting

Safety first: Ensure the area is clear and the generator is safe to start manually.

  • Review event log: Use the controller menu to view the last fault that occurred during exercise (e.g., OC, LOP). Address that underlying issue first.
  • Check battery and charger: Confirm the battery is fully charged and the charger is operating correctly.
  • Verify fuel and valves: Ensure gas valves are open and fuel is available at the time the exercise is scheduled.
  • Exercise settings: Enter the controller setup and verify the exercise day, time, and duration are correctly programmed per the Briggs & Stratton manual.
  • Manual test: Run a manual exercise cycle to confirm reliable starting and running. The EXER fault should clear after a successful exercise.
Advertisements

Repair Difficulty

Easy 2/5
Advertisements