Centurion
Corrosion and Oxidation Damage
Corrosion on battery terminals and metal parts inside Centurion generator enclosure.
Advertisements
Possible Causes
Battery off-gassing due to overcharging, Salt air exposure, Water ingress, Inadequate ventilation around battery
How to Fix / Troubleshooting
Safety first: Turn OFF generator and disconnect battery before cleaning corrosion.
- Neutralize corrosion: Use a baking soda and water solution to clean battery terminals and corroded metal surfaces, then rinse and dry.
- Apply protectant: After cleaning, apply dielectric grease or battery terminal protectant spray.
- Check charger voltage: Verify that the Centurion charger is not overcharging (typically 13.2–13.6 VDC float).
When to call a technician: If corrosion has damaged wiring or terminals, a technician should replace affected components and verify charger operation.
Advertisements
Repair Difficulty
Easy
2/5
Required Part
Battery Cables
Check Price on Amazon