Champion Auto-Start / Transfer Logic Failure

Generator does not start automatically during a utility outage but starts fine in MANUAL mode

Advertisements

Safety Warning

This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.

If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.

Advertisements

Possible Causes

Controller not in AUTO mode, misconfigured exercise/auto-start settings, open control wiring to ATS, failed ATS start relay

How to Fix / Troubleshooting

Safety first: Only qualified persons should simulate outages by operating main breakers. Keep the generator in a safe state while testing.

  • Verify AUTO mode: Confirm the controller is set to AUTO and no lockout conditions are active.
  • Check event log: Review the controller event history (if available) for missed start commands or faults.
  • Inspect control cable: Check the low-voltage cable between generator and ATS for damage or loose connections.
  • Simulate outage (technician): With a technician present, open the main utility breaker to see if the ATS sends a start signal to the generator.

If the generator never receives a start signal, the ATS control board or wiring is suspect.

Advertisements

Repair Difficulty

Hard 4/5

Required Part

Automatic Transfer Switch Control Board
Check Price on Amazon