Fault Code 1150
Cummins
Low Fuel Level Detection
Controller displays Fault Code 1150 – Fuel Level Low (if tank sender connected); generator may not start or may shut down
Advertisements
Possible Causes
Actual low fuel in day tank, Faulty fuel level sender, Wiring fault between sender and controller, Incorrect sender calibration
How to Fix / Troubleshooting
Safety first: Disable automatic start. For diesel, avoid open flames; for gas, ensure area is ventilated.
- Verify fuel level: Physically check the fuel tank or day tank gauge. Refill with the correct fuel if low.
- Sender inspection: Locate the fuel level sender on the tank. Inspect wiring and connector for corrosion or damage.
- Sender test: If possible, measure sender resistance and compare to Cummins specifications. Replace the sender if readings are out of range.
- Calibration: Some controllers allow sender calibration; verify settings match the installed sender type.
- Reset: After correcting fuel level or sender issues, clear the fault and confirm proper level indication.
Advertisements
Repair Difficulty
Easy
2/5
Required Part
Fuel Level Sender
Check Price on Amazon
We may earn a commission from links on this page.
Advertisements