E09
DuroMax
Undervoltage / Weak Excitation
Generator runs but E09 displayed and output voltage is too low or unstable
Advertisements
Safety Warning
This repair may involve working with high voltage components or water connections. Always unplug the appliance before removing any panels.
If you are not confident in your ability to perform this repair safely, we strongly recommend contacting a professional technician.
Advertisements
Possible Causes
Failing AVR, Shorted stator winding, High resistance connection at alternator output lugs, Excessive load beyond rated capacity
How to Fix / Troubleshooting
Safety first: Disconnect all loads, open the main breaker, and shut down the generator. Disconnect battery negative before opening panels.
- Measure no‑load voltage: Start the generator with no load and measure output. If voltage is normal with no load but drops severely under small load, suspect a weak AVR or stator issue.
- Inspect output lugs: Tighten all output terminal bolts and check for heat discoloration or melted insulation. Clean and re‑terminate any overheated connections.
- Check for overload: Confirm that the connected load does not exceed the generator's continuous rating. Remove large motor loads and retest.
- Replace AVR: If wiring and load are correct but voltage remains low or unstable, replace the AVR with a DuroMax‑approved unit.
- Stator testing: If a new AVR does not fix the problem, a stator winding may be shorted. This requires resistance and insulation testing by a qualified technician and likely stator replacement.
Advertisements
Repair Difficulty
Hard
4/5
Required Part
Stator Assembly
Check Price on Amazon